|
What’s New for
NEC-2008?
Concrete Encased Electrodes.
By Keith Lofland
A proposal was submitted for NEC-2008
to recognize a vertically run concrete-encased electrode as well
as the currently accepted horizontal concrete-encased electrode.
This proposal, ROP 5-152, was originally rejected but was
ultimately accepted in the comment stage by comment 5-86. There
seems to be no technical justification to require that
concrete-encased electrodes (rebars) be located horizontally and
not to accept the vertical position within that portion of a
concrete foundation footing or pier.
One of the reasons that a
concrete-encased electrode is so effective is due to the fact
that the concrete has a much larger surface area in contact with
the earth than other electrodes. In addition, the steel rods or
copper conductors in the concrete are in direct contact with the
concrete. These two facts exist whether the rebars are at the
bottom of the foundations or vertical in a column or pier.
Concrete gives out moisture slowly wherever it is in contact with
the earth, not just at the bottom of the foundation. Concrete
absorbs moisture quickly and loses moisture very slowly. The
mineral property of concrete and its inherent pH means concrete
has a supply of ions to conduct current. The moisture present, in
combination with the surrounding soil, makes for a good conductor
for electrical energy or lightning currents.
Another element involving
concrete-encased electrodes that received some clarification for
NEC-2008 was multiple concrete-encased electrodes present at a
building or structure. At several large commercial (and some
residential) buildings, it is very possible to have several
sections and perhaps multi levels of a foundation with isolated
rebar sections that individually would meet the definition of a
concrete-encased electrode, but with none of these separate
sections being tied together by any intentional conductive path.
The question arose in the past concerning these multiple
concrete-encased electrodes pertaining to whether or not one or
all of these multiple qualifying electrodes are required to be
connected and used in the grounding electrode system. It was made
clear by the addition of the last sentence of Section
250.52(A)(3) in NEC-2008 that only one of these qualifying
sections of a concrete-encased electrode be required to be
connected and used in the grounding electrode system. The
conclusion can be reached that subsidiary conductivity is
provided between these separate sections of steel reinforcing
bars by the eventual common concrete encasement.
|